365B Long-Ranger Computing Timer |
- Industry standard digital timer
- Adjustable range 0.01 sec. to 999 hours
- High brightness VF display
- High noise immunity
- UL recognized
|
|
|
Product Detail: |
The ATC 365B Timer is microprocessor-based digital timer with three rotary knobs for setting and adjustment of the Preset. The Preset can be any three-digit value from .01 Sec to 999 Hrs. The Decimal and Range are switch selectable. The high-intensity blue vacuum fluorescent display is DIP switch selectable to Timeup or Timedown. Two heavy-duty 7A DPDT relays provide instantaneous, interval or delayed output control. Plug-in panel mounting allows easy replacement without the removal of field wiring.
COMPUTATION: Through its internal microcomputer, the 365B keeps track of the set point throughout the time cycle. Whenever there is a change in set point, even during a cycle, it instantly re-computes the time remaining and accurately determines time-out. This unique capability is especially valuable in the time-down modes as it allows you to shorten a cycle without loss of accuracy.
POSITIVE RESET TIME AND PULSE LENGTH: Digitally clocked by the microcomputer, the 365B’s reset time is consistently of the same duration, regardless of variations in line voltage, power supply or time cycle. As a result, the 365B is not subject to false reset from momentary power interruptions (less than 30 ms). When the 365B operates in repeat-cycle mode, the output pulse is also digitally clocked so that both its occurrence and duration are consistent.
WIDE RANGE: Each 365B Long-Ranger covers the overall span of 0.01 sec. to 999 hrs., in nine switch-selected ranges of 0 to 9.99,99.9 or 999 sec., min. or hrs. The timer can be optimized within any selected range simply by removing appropriate selector knobs (e.g. with the timer in the 9.99 sec. range, you can obtain a tamper-proof span of 0.99 by setting the left selector at 0 and removing the knob).
PROGRAMMABLE DISPLAY: Depending on the position of an internal jumper, the 365B’s three-digit cycle progress display will time UP to or DOWN from the set point; after time-out, it will either STOP or GO (i.e. display the time elapsed after time-out). To the right of the three-digit display, a timing bar “–” blinks once per second during the timing cycle and rapidly after time-out. At left, a marker “∇” turns on when the delayed relay is energized. The 365B is also available without display but with a pilot light that blinks once per second during the cycle and rapidly after time-out.
NOISE IMMUNITY: The 365B has formidable defenses against noise: transformer power supply, full-wave bridges, buffered logic. Furthermore its microcomputer detects; and rejects; noise pulses that manage to penetrate its defenses. No industrial timer has ever offered greater noise immunity.
RELIABILITY AND RUGGEDNESS: ATC firmly believes that no industrial timer has ever achieved a higher level of reliability and ruggedness. The 365B’s electronic components have no moving parts and are assembled, virtually without hand wiring, from computer-tested circuit boards. Its few mechanical components have been selected for reliable service; the two load relays have a life expectancy of 100,000,000 operations and heavy-duty contacts rated at 7 amps; and the three rotary set point selector switches exhibit extremely low wear.
COMPACT, PLUG-IN AND DUST-TIGHT: Packaged in a 72mm2 DIN housing, the 365B occupies 40% less panel space than conventional timers. It is a true plug-in timer that can be replaced in seconds without disturbing housing or wiring. The 365B is also fully gasketed and O-ring sealed to be dust and water-tight.
SELF DIAGNOSTICS: The time will display "FAIL" anytime there is a problem or the knobs are in between digits. |
Part Numbers: |
Create Model Number >>>>> |
365B |
xx |
xx |
xx |
P |
xx |
Range |
300 |
L |
30 |
P |
X |
0 to 9.99, or 99.9 or 999 sec., min., or hr |
Special |
000 |
Voltage & Frequency |
125 VDC |
24 VDC |
N |
120 VAC, 50-60 Hz |
Q |
240 VAC, 50-60 Hz |
R |
24 VAC, 50-60 Hz |
T |
Special |
K |
Arrangement |
With display, ON-Delay/Time up or down and stop
(reset on power failure) |
Time up or down and go |
50 |
Features |
Basic plug-in unit |
Standard Unit |
Special |
K |
|
Options: |
| Accessories |
| 0353-260-27-00 |
Surface mounting bracket kit |
| 0305-265-61-70 |
Retrofit kit
|
Direct Replacement for 365A
|
|
Purchase Details: |
 |
Product Contact: |
|
|
| Specifications: |
| Models |
Arrangement “30,” with digital display available for On-Delay operation at 120, 240 or 24 VAC; and 24, 48 or 125 VDC |
| Ranges |
Switch-selectable ranges of 0-9.99, 0-99.9 and 0-999 sec., min. or hrs. |
| Timing Modes |
Single Cycle |
interval or delayed |
| Repeat Cycle |
pulse-clocked at 50 to 80 ms (will be constant for a given unit) |
| Reset Time |
Clocked at 60 mSec |
| Display Cycle Progress |
3 digit display, 0.3 inch, high-intensity, blue programmable: DOWN and STOP, DOWN and GO, UP and STOP or UP and GO |
| TIME-OUT |
“∇”display (left); energized at time-out. |
| Timing Bar |
display (right); blinks once per second during cycle, rapidly after time-out. |
| Clock Input (terminal 15) Voltage Model |
120VAC Model |
95-132 VAC, 10mA max. current at |
| 240VAC Model |
190-264 VAC, 10 mA max. current at 240V |
| 24VAC Model |
19.2-26.4 VAC, 20 mA max. current at 24V |
| 24VDC Model |
19.2-26.4 VDC (5% ripple), 5 mA max. current at 24V |
| 125 VDC Model |
19.2 to 26.4 VDC 50mA DC Max. |
| 125 VDC |
100 to 150 VDC 15mA DC |
| Temperature Rating |
32 to 140°F (0 to 60°C) |
| Power Requirements |
120 VAC |
95-132 VAC, 50 or 60 Hz.
Inrush — .3A.
Running 0.06A at 120 VAC |
| 240 VAC |
90-264 VAC, 50 or 60 Hz.
Inrush — .15A.
Running — 0.03A at 240 VAC |
| 24 VAC |
19.2-26.4 VAC, 50 or 60 Hz
Inrush — 1A.
Running — 0.25A at 24 VAC |
| 24 VDC |
19.2-26.4 VDC, 5% ripple
Running — .120A AT 24 VDC |
| Load Relay |
Number |
one instantaneous and one delayed. |
| Type |
DPDT, Form C. |
| Operate Time |
P 13 mSec, max. |
| Release Time |
10 mSec, max. |
| Contact Ratings |
7A at 120, 240 or 24 VAC 1/6 HP |
| Life |
100 million operations (no load) |
| Repeat Accuracy |
± .001% ±.010 sec. of setting |
| Setting Accuracy |
±.01% + .030 sec. of setting |
| Terminals |
16 screw terminals accessible at rear |
| Housing |
72mm2 DIN size; plug-in design; fully gasketed, dust and water-tight in panel mounted installations. |
| Mounting Accessories |
Standard |
hardware is provided for front-of-panel mounting. |
| Optional |
Surface-mounting brackets with front-facing terminals. |
| NEMA 12 molded case (1 timer) |
| Weight |
NET: AC 1 lb., 6 oz., DC 14 oz. |
Shipping: AC 2 lbs. DC 1 lb., 8 oz. |
|
|